PRODUCT “A2”

INSTALLATION AND OPERATION MANUAL

VERSION 0.3, JANUARY 2002

 

 

 

The “A2” load control governor is designed to manage loads and govern frequency when used on independent small hydro plants

 

Without external relays, can be used on plants of size 1 KW to 12 KW, 240 volts (60 Hz), or 220 volts (50 Hz) single phase.

 

With external relays, can be used on plants of size 1 KW to 114 KW, 240 volts (60 Hz) or 220 volts (50 Hz) single phases, 208/240 volts (60 Hz) or 380 volts (50 Hz) three phase.

 

 

 

THOMSON AND HOWE ENERGY SYSTEMS INC.

8107 HIGHWAY 95A

KIMBERLEY, BRITISH COLUMBIA, CANADA  V1A 3L6

PH.:     (250) 427-4326           FAX: (250) 427-3577

INDEX

PAGE

 

·        INTRODUCTION AND ESSENTIAL READING.... ................................…....3

·        THEORY OF OPERATION..... ..........................................................…….......6

·        DESCRIPTION AND SPECIFICATIONS... ......................................….........11

·        WIRING INSTRUCTIONS WITH EXAMPLES.. ...............................………14

·        CASE HISTORY ........................................................................................…..15

·        COMMISSIONING INSTRUCTIONS ....................................................…...17

·        TROUBLESHOOTING INSTRUCTIONS........ ....................................…......18

·        SPARE PARTS AND REPAIR SUPPLIES...................................................... 22

·        WARRANTY AND DISCLAIMERS............................................................... 23

·        GLOSSARY OF TERMS................................................................................. 24

·        FACTORY OPTIONS. .........................................................................……...30

 

 

 

 

 

 

 

 

 

 

Dear Customer:

 

Congratulations on your purchase of a Thomson and Howe product.  You have bought the most advanced small hydro-electric governor system in the world.  We strongly recommend that you read the rest of this manual at your earliest convenience in order to make use of the governor’s advanced features and to maximize the usefulness of your plant.

 

We wish you many years of reliable generation.  Do not hesitate to call or write us if you have questions or need advice.

                                                           

Essential note #1 - Main Loads

 

You must connect two equal sized loads to the outputs contained inside the product “A2”.  These loads may only be simple resistance heating elements, and cannot have any control devices (e.g. thermostats, switches) that may interrupt the connection.  These loads will be controlled internally by the governor.  They may be sized at up to a maximum of 6000 watts (@ 240 volts) each or as  large as required to match your maximum power generation, whichever is smaller.  These two internally controlled loads are called the “main load” in this manual.

 

Essential note #2 - For Plants of More Than 12 KW Output

 

If the amount of “main load” is not sufficient to absorb the maximum output of the generator, then additional loads must be controlled externally by the governor in order to prevent overspeeding.  These additional, external loads can be connected to relays that are controlled from the governor by means of low voltage signal wires.  Any loads that are required to prevent overspeeding must always be available in order to guarantee sufficient system load.  If it is necessary to waste the energy from certain of these loads in order to assure sufficient loading for the generator, then these loads are known as “waste loads”.

 

Essential note #3 - Connecting Additional Externally Controlled Loads

 

a)         The externally controlled load to each step control output (the green terminals on           the side) should not exceed about 1/2 of the “main load” (see note #1).  For            instance, if two 3 KW loads are directly connected to the governor, then each step   should not control more than 3 KW.

 

b)         When connecting waste load relays to the governor, start at control output #8,   working down towards lower numbered outputs, connecting as much waste load         as necessary to prevent overspeeding.  Overspeeding will be prevented when the       total guaranteed external load plus the two main governor loads exceed the        maximum output of the generator.

 

c)         For three phase systems, try to balance the controlled loads between the three   phases.  To balance loads usually requires a minimum of four relays.

 

d)         If the half-step output is used, only a solid state relay should be connected to this           particular control output.  Read the manual carefully if this output is to be used.     95% of installations do not require this output to be used.

 

e)         Useful user loads that the user wishes to have managed by the governor should be         connected to     step outputs #1 and up, with the highest priority load connected to    step output #1, and working      down in priority as higher numbered step outputs      are used.

 

Essential note #4 - Initial Computer Module Switch Positions

 

The internal module has four switches.  For most installations, turn #1 and #4 switches on, leave #3 switch off.

 

Essential note #5 - Switch 2 Detail

 

If externally controlled loads are not used, or if they only control loads that waste excess generation, then you may leave #2 switch off.  However, if you have even one useful load connected to a externally controlled relay, then turn switch #2 on to inform the computer that external loads should be turned on whenever possible.

 

Essential not #6 - Main Load Vulnerability

 

The loads connected directly to the governor must be of high quality and immune to shorting out.  If these loads burn or short out, then the “triac” solid state power devices may be damaged and require awkward repair.

 

Essential note #7 - Is the Governor Working?

 

Leaving aside any other considerations or complications, note that if the frequency meter is indicating a steady 60 Hz (optionally 50 Hz), then the governor is doing its prime function of governing the system frequency correctly.

 

Essential note # 8 - Reading the Load Meter

 

The load meter will read the amount of power delivered to the “main loads” only, not the externally controlled loads.  The power is read as a percentage of the maximum rating of the main loads.  For instance, if two 3 KW loads are connected, and the meter reads 10% then the power going to the two main loads is (3KW + 3KW) x 10% = 0.6 KW = 600 watts.  Electricians - please note that reading the voltage output to these two loads in order to calculate power output will provide erroneous results.  Use the load meter provided.

Essential note #9 - Why are the Red and Yellow Lights Dark?

 

Each red or yellow light will only light up if the governor has turned that particular step output on, and if a complete control circuit exists from that output to a externally controlled relay.  If for some reason, the control circuit is broken, this fact is immediately obvious because the light will go dark unexpectedly.  If you wish the lights to indicate even if they are not controlling relays, then you may install wire jumpers between the terminal pairs of unused outputs.

 

Essential note #10 - Main Load Sequence

 

The main load connected to terminals #3 and #4 will be turned on fully by the computer first.  The voltage supplied to this load will increase from zero to maximum as the load meter increases from 0 to 50%.  From 50% to 100% indication on the load meter, the first load will be held at maximum and the second load connected to #5 and #6 will vary from zero to maximum voltage.

 

Essential note #11 - The Green Light is Dark

 

The green light is a memory device.  Its function is to tell you that an abnormal operating condition has occurred since the governor was last energized.  It does not otherwise affect the operation of the governor.  It can be reset by the optional push-button, or by shutting the plant down momentarily.

 

Essential note #12 - The Percent Load Never Reads Very High and the Steps Refuse to Stay on.

 

Do not blame the governor.  The governor cannot create power, it only manages the power available from the generator.  If insufficient power is available, then the governor will automatically reduce the number of loads on to try to maintain correct operating speed and frequency.  If the power is much less than expected, the first thing to check is the penstock pressure.

 

Essential note #13 - Additional load management

 

You might be interested in the product “C” if your site has any of the characteristics listed below.  The product “C” will work on the same system as a product “A”, and control eight additional loads without any control interconnections to the product “A”.

 

a)         Loads to be managed that are remote from the intended site of the governor.

 

b)         You require more than eight levels of load management.

 

c)         The loads are spread over a large area, such as a community

 

d)         You plan to operate the system from more than one source of power.

THEORY OF OPERATION

 

GOVERNING DEFINITION:  The definition of governing with mechanical equipment is the control of speed.  Since the speed of an A.C. generator is synchronized exactly to the frequency of the power, governing of an A.C. power system is synonymous with control of frequency.

 

A COMMON EXAMPLE OF A GOVERNOR:  Governing of power systems is done by maintaining a precise balance between the power being generated and the power being consumed at every moment in time.  One analogy for this process is that of a driver of a car on a highway.  He must constantly monitor the speed of the car and adjust the throttle of the car to maintain constant speed.  A cruise control will do this function of speed control automatically for the man and hence is a type of governor.  Note the following:

 

i.          The speed of the car is monitored by the governor (the person or the cruise       control).

 

ii.          Without adjustment, the speed of the car will increase if the demand for power   decreases (i.e. tail wind, downhill slope).

 

iii.         Without adjustment, the speed of the car will decrease if the demand for power             increases (i.e.    head wind, uphill slope).

 

iv.         The output from the engine will be adjusted by the governor to compensate for changes in load when a change of speed is detected.

 

TRADITIONAL HYDROPLANT GOVERNING  The task of a traditional mechanical water governor is conceptually identical to the above analogy, but it is expressed a little differently:

 

i.          The frequency of the generator is monitored by the governor.

 

ii.          Without adjustment, the frequency of the generator will increase if the demand for          power decreases.

 

iii.         Without adjustment, the frequency of the generator will decrease if the demand for power increases.

 

iv.         The output from the turbine will be adjusted by the governor to compensate for changes in load when a change of frequency is detected.

           

A MODERN ALTERNATIVE  An increasingly popular method is avoiding all mechanical equipment required for controlling water.  These governors perform the basic governing function by automatically maintaining the demand for power from a generator in balance with the amount of power can supply. 

The balance is maintained by control over lower priority loads that may be adjusted to compensate for changes in turbine output or for any user switched loads that are turned on or off elsewhere on the system.

 

ADVANTAGES OF LOAD CONTROL GOVERNING  The generator always generates the maximum power possible.  The generation not immediately required is used up in secondary loads that are controlled by electronic equipment.  If these secondary loads can be used for useful purposes, the overall system efficiency can be extremely high, whether used with run-of-the-stream or water storage capable sites.  Other advantages are as follows:

 

i.          Since the control is by electronic means, the response of the governor to changes           in frequency can be faster and more accurate than mechanical means of governing.

 

ii.          Governing by control of water is complicated by the effects of water hammer.  Water hammer results from having to accelerate and decelerate the moving water in the power plant and penstock in order to vary the flow through the turbine.  These effects can be severe if the water flow is changed too quickly.  Water hammer induced pressure fluctuations create governing difficulties if not corrected for.  Water hammer problems are reduced in large hydro-power plants by keeping the length of the pipelines as short as possible, by reducing the speed of operation of the governor, (possible only if the loads change slowly enough),  or by installing surge towers to absorb the impact of flow changes.  If the governing is done by load control no quick changes are necessary.

 

iii.         No moving parts.  Mechanical governing requires relatively fast and accurate     mechanical movement.  These devices necessary to control water add to the    turbine expense.

 

iv.         The generally least expensive types of turbines do not have any simple way to    control water.  Industrial pumps, for example, can be applied as low cost turbines     by operating them backwards, but of course, do not have any inherent method for        controlling water but must use load control.

 

v.         Little or no custom engineering is required, because the governing action is not   affected by site dependent characteristics such as length and size of the penstock.

 

T.H.E.S. GOVERNOR FUNCTIONS  The Thomson and Howe Load Control Governors are designed to perform three jobs in a hydro-electric installation:  First of all these governing systems will govern by load control very accurately.  But a governor system installation will also provide two more functions:  It will look around for additional loads to turn on in order to maximize the usefulness of the plant -- this is known as load management; and also it will prevent overloading of an hydro-electric plant by shedding loads at peak demand periods or during low water -- this is know as peak demand control.

 

FREQUENCY MONITORING  T.H.E.S. Load Control Governors monitor only the frequency of the power system which is exactly the same at any point on the system.  Frequency is also proportional to the rotational speed of  your alternator.  The Load Control Governor will hence monitor and control the speed of your A.C. generator from anywhere on the power system.

 

INSTALLATIONS WITH A LARGE LOAD/GENERATION RATIO Peak demand control becomes most important on systems that only have a small generator connected, since the loads are very likely to exceed the output of the generator.  In extreme cases, only loads that must stay on no matter what (e.g. inside lights) would be connected directly to the generator.  All other loads would be connected to relays so that they will be turned off if the power is needed elsewhere.

 

INSTALLATIONS WITH A SMALL LOAD/GENERATION RATIO  In a system that has a relatively oversized generator, the loads originally connected are not so likely to exceed the output of the generator.  Hence peak demand control is less important.  All user loads may be connected directly to the generator without fear of overloading.  The user may, however, have a motivation to improve the economics of running the plant by finding additional low priority loads to use up the excess generation.  This will require load management.

 

A NUMERICAL EXAMPLE OF POWER DIVERSION  A generator is producing 60 KW, delivering this power to 35.4 KW loads that the user has switched on at this particular time.  The governor has main loads totaling 12 KW connected, and each of eight load management relays has a load of 6 KW connected.  Without a Load Control Governor or controlled relays, the generator would run away into overspeed because of the 24.6 KW excess power being generated;  However, the Load Control Governor will respond quickly and first of all add on the 12 KW main governor load.  There still remains a surplus of 12.6 KW, so the Governor will quickly turn the three relays on, creating an automatically controlled load of 12 + 3 x 6 = 30 KW plus the user controlled load of 35.4 KW.  The 5.4 KW excess load will be adjusted for by backing off the main load from 12 KW back to 6.6 KW, exactly balancing generation and load.

 

60 KW generation =     35.4 KW (demand)

                                    6.6 KW (main Governor load)

                                    18.0 KW (three relay loads at 6 KW each)

 

 

 

 

 

 

 

 

 

SMALL SYSTEM EXAMPLE  A 5 KW generator is running, supplying a single household.  The user has connected the loads as follows:

 

            DEMAND- lights, convenience outlets (maximum load 5 KW, minimum load 0                         KW)

 

            MAIN CONTROLLER-two 2.5 KW hot water elements (large tank) switches to         two 2.5 KW baseboard heaters when the thermostat is hot.  NO thermostat on   baseboards.  If the house gets too hot, install a switch to switch power                          in the summer to the outside.

 

            RELAY #1 -                 clothes dryer (small, no more than 2 KW)

            RELAY #2 -                 clothes washer (1.0 KW)

            RELAY #3 -                 kitchen fridge, deepfreeze (1.0 KW maximum)

            RELAY #4 -                 second hot water element (2 KW) insures hot water has this                                                        level  of priority.  Thermostat controlled.

            RELAY #5 -                 kitchen / bathroom baseboards on thermostats (maximum 2                                                          KW)

            RELAY #6 -                 living room baseboards on thermostats (maximum 2 KW)

            RELAY #7 -                 bedroom baseboard heaters on thermostats (usually turned                                                           off during the day, maximum 2 KW)

            RELAY #8                   spare

 

Note the following with regards to this example installation:

 

1.         Things that a person expects to have available on demand, lights, radio, T.V.,    toaster, are directly connected to the generator, but that these loads never exceed a   total of 5 KW at any one time, Providing peak demand control by avoiding             overloads.

2.         The governor main loads are never turned off.  These loads ensure that the         generator will never overspeed due to too many loads being turned off.

3.         Note that the loads connected to the relays in this example never exceed 3 KW per       step (less than   two/thirds of the 5 KW main governor loads).

4.         Note that the loads connected to the relays are in order of priority, and that any of         these loads may be turned off if there is insufficient power.

 

OPERATING RANGE  A load Control Governor can be used on any size generating system.  However, it can only maintain frequency control if the power system always has a small surplus to sink into the Load Control Governor, otherwise, the Load Control Governor would no longer have any load to maintain control with.  The system frequency could drop because of an overload condition.  Conversely, the generator should not have a power surplus larger than the maximum that the Load Control Governor system can sink, otherwise the frequency could rise because of an underload condition.

 

CONSTANT LOADS  A T.H.E.S. Load Control Governor system may, however, be used on a generator of  capacity larger than the Load Control Governor load.  In this case, however, constant base loads must be connected continually to the generator in order to reduce the maximum surplus power that could possibly become available.

 

MAIN UNIT OUTPUTS  The main unit has two direct high-power (SCR) outputs that finely control the frequency by continually adjusting the output voltage throughout the range from 0 to 230 volts as required.  The loads connected to these output(s) must be simple heating elements because of the fluctuations (i.e. no motor-driven equipment).  The load connected to terminals #3 and #4 is of higher priority and will come on first before the load connected to terminals #5 and #6.

 

MAIN UNIT LOADS  Since the loads connected directly to the governor are subject to voltage variations, and hence are limited to simple resistance elements, the Load Control Governor system has the ability to prefer to turn on relay loads whenever possible.  The relay loads, as they are turned on, reduce the power diverted to the main governor loads.  This preference is obtained by turning #2 module switch up.

 

SUGGESTIONS FOR LOADS  The Load Control Governor needs guaranteed loads that are capable of absorbing the output of the generator for long periods of time without problems.  A partial list of loads that can be considered follows, however, most often guaranteed loads are simply waste loads, since this is simpler.

 

            1.         Swimming pool heaters

            2.         Concrete imbedded heating cables

            3.         Hot water heating (with high temperature relief valve or pump).

            4.         Soil heating cables or greenhouse heating

            5.         Snow melting cables in driveways

            6.         Furnace heating elements (with a backup heat source)

 

HALF STEP RELAY  The Load Control Governor has a special output to control a relay separate from the eight load management relays for some installations.  This relay may be sized up to two thirds of the total main load connected.  Since this relay is switched quite frequently, it should be a solid - state relay and the load should be considered as a lowest priority load, the same as the main loads.  This half - step load must also be always available for turning on.

 

REASONS FOR USING THE HALF-STEP  There are two reasons for using this half step relay: First, on large systems, the maximum load that may be connected to any (or all) of the eight load management relays is increased to double the load connected to the half step load.  This allows much higher power capability at little extra cost; Second, on small systems, larger appliances may be controlled by relays since the half step load turns off the instant that each of the eight relay steps is turned on, reducing the impact of each relay load.

 

RELAY PRIORITY  The Load Management Loads are switched remotely from the main unit by means of 10 milli-amp current loops to controlled power relays.  One to eight relays may be turned on or off as available surplus power permits, but lower numbered relays are turned on, and also the higher numbered relays, if turned on, will be turned off first.  This priority step design can provide the user with the following benefits:

 

1.         Since these eight steps are switched in strict order of priority, the user can connect         more    important loads to the lower numbered steps, and less important loads to   the higher numbered steps.  This will ensure that the power that is available will     always go where it is most needed.

 

2.         On a three phase system, the user need only arrange relay controlled single phase          loads on each   of the phases to balance phase currents to an acceptable amount.        No expensive three phase Governor is required.

 

3.         The use of relatively inexpensive relays to switch the majority of the loads reduces          the overall cost, especially for larger plants.

 

4.         The use of phase switched devices such as triacs or SCRs crates large transient disturbances in the power waveform.  The use of relays for the majority of the load reduces this effect to a low level.

 

TESTING OF RELAY LOADS  If the “optimizer” is turned on (switch #2 in the up position), then every minute or two the Governor will attempt to turn on the next lower priority step not already turned on, using power available from the main load.  If enough power is available, the step will stay on,  If not, then the step will turn off and the Governor will wait until more power is available before trying again.  With sufficient power, the process will end when all steps are on.  The low priority main load will hence be reduced as low as possible.

 

DESCRIPTION AND SPECIFICATIONS

 

ENCLOSURE  The T.H.E.S. Load Control Governor is housed in a non-ventilated, gray enamel painted steel enclosure.  The enclosure is 12 inches by 14 inches high by 6 inches deep.  The gaskets are foam rubber.  The door has a piano hinge on one side and two steel clamps on the other side.

 

FREQUENCY METER  The front panel has a frequency meter which reads from 0 to 100 hertz with 2% F.S. accuracy.  The user should note that when the controller is functioning normally, the controller is more accurate than the meter, however, the meter is useful for monitoring fluctuations or abnormal situations.

 

 

LOAD METER  The load meter on the right indicates the percentage of the main load maximum power capability that is currently being used.   For instance: if 2 KW is being dumped into two 3 KW loads (totaling 6 KW) connected to the main governor outputs, then this meter will read 33%.  If this dump power increases to 4 KW, then the meter will read 67 %.

 

LIGHTS  The eight red lights indicate the status of the Load Management steps.  These lights will only indicate when the load management step turns on and a relay is connected to that step’s terminals.  The lower left yellow light indicates the status of the half step.  This light otherwise behaves the same as the eight load management lights.  The lower right green light is normally lit when the controller is functioning normally, it will go out if the Load Controller is not supplied with power, or if the controller has detected under 55 Hz or over 65 Hz for more than a few seconds, or if the time error counter has overflowed.  This light will also flash if the computer discovers an internal failure.

 

SIDE OF PANEL  The side of the panel has one terminal pair near the top.  This is the half step control output.  The eight lower terminal pairs are below the aluminum heat-sink, they are arranged as follows:

 

1.         2.

3.         4.

5.         6.

7.         8.

 

The positive (source) terminal is always on the right and painted red.  The negative (drain) terminal is always on the left and silver in colour.

 

CONTROLS  Inside the enclosure is a small control box with four switches.  The left-hand switch (#1) is the step speed adjustment, and selects either normal (on) or slow (off) step switching speed.  If switch #2 is on, the computer will operate with a preference to turn on relays in order to reduce the main unit loads (see “relay testing”).  The two right-hand switches set the frequency accuracy of the Controller.  Note that time-keeping and steady-state frequency accuracy is maintained in any position.

 

SUPPLY VOLTAGE  To terminals #1 and #2 inside governor.  This supply is used both for the governor electronics, and to power the two main unit loads connected to terminals #3 through #6.  200 volts to 240 volts is acceptable for standard governors.  120 volts is the optional voltage.

 

GOVERNOR INTERNAL POWER CONTROL CAPABILITY  3000 watts per output at 120 volts, 6000 watts per output at 240 volts, 6000 watts per output at 208 volts.

 

 

 

ACCURACY OF FREQUENCY CONTROL DURING LOAD CHANGES  Full governing action can be set for the following sudden frequency deviations:  plus or minus 4 hertz, 2 hertz, 1 hertz, or 0.5 hertz.  This is equivalent to setting the proportional gain in a typical process controller.  Due to the inclusion of the equivalent of an integral term, these settings affect the immediate response only, within a few seconds, the governor will return the frequency to 60 hertz (optionally 50 Hz) no matter what the setting.  Large, sudden load changes requiring several relay step changes may cause the frequency deviation to exceed these settings momentarily.

 

ACCURACY OF STEADY STATE FREQUENCY CONTROL  Standard controllers are not tested for frequency accuracy since the quartz crystals have inherently high accuracy.  Sample testing of unadjusted units indicate a typical accuracy of 0.005 Hz.  Optional calibrated units are supplied with an internal frequency adjustment.  Factory calibration is usually accurate to 0.0003 Hz, or about 15 seconds per month with normal ambient temperature changes.  Temperature changes will affect frequency slightly, so governors installed in unheated powerhouses will not have as high a frequency accuracy as governors installed in constant ambient temperatures.

 

INTEGRAL TERM RESET SPEED  If a load change results in a new frequency due to the action of the proportional term, the integral term will reduce the frequency error by half every 1.5 seconds.

 

CLOCKS WILL RETURN TO CORRECT TIME AFTER LOSS OF GOVERNING  The timekeeper (which is not the integral term mentioned above) is allowed a maximum 0.1 Hz deviation to correct clock times following a loss of governor control due to overspeeding or overloading.  0.1 Hz translates to 6 seconds of correction every hour, 17 minutes every week.

 

POWER CONSUMPTION  10 watts (1 watt for newer CMOS modules), plus approximately 0.5% of the power delivered to the load at 240 volts.

 

SLEW RATE  Triac loads can typically change from zero load to full load (or vice-versa) in 3 cycles (50 milli-seconds) for normal frequency changes.  With switch #1 in the fast (up) position, step loads will step in at 1/4 second intervals for small errors in frequency (2 seconds for all eight).  Large errors in frequency trigger a double speed step change rate of 125 milli-seconds per step, higher errors trigger a triple speed stepping rate of 83 milli-seconds per step (2/3 of a second for all eight steps).  With switch #1 in the slow (down) position, all step switching times are four times slower.

 

RELAY TESTING  The Controller will normally try to turn main steps on at the rate of one per minute if power is being delivered to the main unit loads.  If a step turns off after being turned on due to insufficient power, then approximately 10 to 25% more power as a percentage of the main load connected must become available before it tries again.  In any case a try is made every half hour to avoid “locking-up”. 

 

This testing action will only occur if switch #2 is in the up position.  If the user does not care how many relays are turned on (e.g. all relay power is wasted anyway), then he would leave switch #2 off.

 

RELAY OUTPUTS ELECTRICAL SPECIFICATIONS  Each positive output is sourced from a switched 20 volt D.C. unregulated source through a 470 ohm resistor and a light emitting diode.  The D.C. supply to all outputs will be energized only when the computer is reset and activated in order to avoid spurious operations.  Each negative output is drained back through a 1000 ohm resistor and a transistor switch to ground (chassis) potential.  Clamp diodes are used on the negative lines to ground to clamp transient voltages.  Common output control lines are not permitted.  Each output must be a separate twisted pair.  Shielded cables are recommended if the routing of the wires is held within one inch of power conductors for more than 2 feet, or if the cable route is more than 100 feet from one building to another.  Connect the cable shield to the chassis of the governor and also to the chassis of external relays.

 

WIRING INSTRUCTIONS

 

CONNECTIONS  The controller usually needs no connections other than the high-voltage power supply and load connections, plus the low-voltage relay control wiring if used.  The controller can be situated anywhere on the system;  It does not have to be installed in the powerhouse.  We actually prefer that the Controller be installed close to the loads to allow more convenient load control.

 

POWER SUPPLY  The load controller main unit requires a single phase power supply rated to carry the current rating of the loads connected.  The following pages provide the internal wiring of the product “A2” panel as well as many suggested wiring diagrams.

 

RELAY WIRING  Note that the relay control wiring is at low voltage and may be wired with telephone or ‘bell’ wire.  Polarity is important, red to red, silver to silver.  Shielded wire may be necessary for long runs between buildings, or if signal wires share conduit with power conductors.

 

 

 

 

 

 

 

A CASE HISTORY

 

The following case history is a combination of many different installations.  None of the names are real, but the basic outline has occurred many times.

 

John Smith owned a remote hunting and fishing cabin that he wanted to turn into an all-season resort.  The key to this ambition was to find an alternative to the noisy, expensive, and old diesel power plant.  John hired ABC Hydro-electric Consultants to provide a proposal on a nearby waterfall.

 

ABC calculated that a plant could be built on the waterfall that would provide almost for all year a 24 KW power output.  John decided to proceed and ABC then issued the specifications to equipment suppliers for quotes.  They specified a mechanical type governor for frequency control.

 

ABC had several phone calls from some of the suppliers that had received the request for tenders.  These suppliers preferred to quote using a Thomson and Howe Load Control Governor.  ABC subsequently modified the specifications to include this approach.  The lowest bids received used the Load Controller and one of theses suppliers was selected.

 

This installation is sometimes typical in that the Load Control Governor was quoted as a direct replacement for a mechanical governor.  Hence simplicity and low first cost of installation was most important in the quote.  In addition, no discussions were held with the owner to optimize the system by discovering what uses he had planned for the power.

 

The Load Control Governor was installed with a main unit load of two 6 KW heating elements that wasted energy into the turbine water, and one dual relay unit.  Each of these two relays controlled another 6 KW waste element.  These relays were connected to steps #7 and #8, as is correct for waste loads.  These loads totaled 24 KW, enough load to ensure that the plant would not be under-loaded.

 

John already had electric lights, convenience outlets, toaster, washer and dryer connected (peak demand 8 KW).  He then also connected an electric stove (peak 10 KW) and 6 KW of thermostatic baseboard heating.  His peak non-governor load was hence kept below 24 KW to avoid overloading the plant.  However, most of the time, he did not use the power for useful purposes.

 

 

 

INITIAL CONFIGURATION

 

                        GENERATOR               ALLOWABLE              WASTE LOAD           AVERAGE USEFUL

                                OUTPUT                                     USER’S LOADS            CONNECTED             GENERATION

 

                                 24                                          24                                24                         5 KW estimated

 

Then winter came.  John found that he was burning wood because 6 KW of baseboard heating was not enough, yet, if he increased the number of baseboard units, he would run the danger of overloading his plant. 

John then re-read this manual and realized that most of his loads could be interrupted by load management relays, allowing far more loads to be connected.  He ordered four relays and connected the 6 KW of baseboards he had and 10 KW of additional baseboards as follows:

 

            Step #1 ---- 4 Kw of baseboard heating

            Step #2 ---- 4 Kw of baseboard heating

            Step #3 ---- 4 Kw of baseboard heating

            Step #4 ---- 4 Kw of baseboard heating

           

Because he had now installed relays on his original 6KW set of baseboards, he was free to add another 6 KW of uncontrolled loads elsewhere on the system, without fear of overloading the generator.

 

WINTER CONFIGURATION

 

                        GENERATOR          USER’S LOADS       WASTE LOADS      AVERAGE USEFUL

                                OUTPUT                                ALLOWABLE         CONNECTED         GENERATION

 

                                         24                               40                                          24                  12 KW (much better)

 

Then summer came.  John found that he was not using the energy because it was warm, hence his return on investment was low.  Also, his guests were using more and more load on demand (e.g. hair dryers at 8:00 A.M.), so he had to move more loads onto relays.  John decided to buy enough relays to add the following loads to attract more business while at the same time, avoiding overload problems:

 

            Step #1 ---- Stove (10 KW peak, almost always lower)

            Step #2 ---- Washer / dryer (peak 5 KW)

            Step #3 ---- Hot water heaters (peak 8 KW)

            Step #4 ---- Baseboard heaters (peak 8 KW)

            Step #5 ---- Baseboard heaters (peak 8 KW)

            Step #6 ---- Hot-tub (peak 8 KW)

            Step #7 ---- Swimming pool (peak 8 KW)

            Step #8 ---- Waste heat elements (9 KW)

            Halfstep --- Waste heat elements (3 KW)

            Governor main loads ---- Waste heat elements (12 KW)

 

In addition to the loads listed above, he was also to connect 24 KW of demand load elsewhere, so that the total useful load connected became 24 + 10 + 5 + 8 + 8 + 8 + 8 + 8 = 79 KW

 

 

FINAL CONFIGURATION

 

                        GOVERNOR            ALLOWABLE         WASTE LOADS      AVERAGE USEFUL

                                OUTPUT                                USER’S LOADS       CONNECTED         GENERATION

 

                24                                   79                          24                           21 KW (close to maximum)

 

COMMISSIONING INSTRUCTIONS

 

PRE START-UP CHECKLIST

 

1.         Is the wiring correct to the governor panel?

2.         Is the governor panel the correct frequency (50 or 60 hertz)?

3.         Is the governor panel the correct voltage for the power being supplied to it?

4.         Are there two loads of the correct voltage connected to the outputs of the          governor, nor more than 4000 watts each @ 120 volts; 7500 watts each @ 208       volts, or 8000 watts each @ 240 volts?

5.         Are the following computer module switches set as follows?

            Sw #1 - off, Sw #3 - off, Sw #4 - on

6.         Is water covering the immersion heaters, if used?

7.         Have all loads been electrically checked with an ohmmeter to ensure no leakage to        ground and the correct element resistance?

8.         Has all electrical equipment been properly grounded to the mechanical equipment          (including the    immersion heater tank if used)?

 

After all wiring has been completed, ensure that the generator runs and generates normally with no power supplied to the Load Control Governor.  This test will ensure that the generator works and that the basic wiring was done correctly.  When performing this test, be sure that the generator does not overspeed by controlling water flow.  Check the generator voltage and ensure that it is reasonable close to what is expected.  Only after the power system is given a clean bill of health should the owner perform the following sequence:

 

1.         Shut down the generator.

2.         Close the breaker to the Load Control Governor.

3.         Gradually open the water valve and start the generator, let the generator speed up          until the Load    Control Governor starts pulling load.

4.         The frequency should then be very close to 60 Hz (optionally 50 Hz) and the Load        Control Governor load meter should be indicating delivery of some surplus power         to the main loads.

5.         Gradually increase the output from the generator, watching that the steps do come         in and that they draw away the excess power.  The frequency should not have to     go above 62 hertz while this is being done.

6.         Once the generator is at full output, try to increase the performance of the          Governor beyond the minimum now set.  Do this by following the lettered     instructions below.  As soon as the governor seems to become unstable (lights             flicker, frequency fluctuates, or it emits a ragged noise instead of a steady buzz),             then go back to the previous step to obtain smooth performance.

 

 

a)         Put switch #4 to the off position and put switch #3 switch up.  This sets a 1 hertz           frequency control.